DAQmx Analog Input (NI9203) not able to read values in LabView

$
0
0

I experience strange behaviour from one of my NI I/O modules.

I have a cDAQ-9188 I/O including two NI9203 Analog Inputs (4..20mA)

I have been used this with related Labview program for a while, until recently moving the whole program on another PC. I migrated the whole NI MAX configuration, and compiled LabView program including all necessary runtimes an DAQmx library. Everything works fine, except the two NI9203 modules which seems to flatten out in Labview (all readings show zero). 

1. The whole cDAQ is working fine with no communication errors. (it has been reserved by the new PC)

2. There are other modules on the same cDAQ (9211, 9265, 9485) working correctly in the same program, means the program sends AO currents and controls the relays.

3. The 9203 is reading the current correctly, when monitored in NI MAX Test Panels, but not in the LV.

4. There was no changes to Labview program nor the DAQ channels recently.

5. The problem occurs both using DAQ assistant and the DAQ virtual channel, even with hard-coded device name and channel.  

6. NI Max v17.0.0, Labview runtime env.2017

 